Bug #1878
Readiness of trench cooling water circuit
100%
Description
Tasks remaining to complete the trench cooling water circuit:
Files
Related issues
Updated by Nebrensky, Henry about 7 years ago
To-do list for TRENCH circuit:
Conductivity meter- PLC (auto vs. manual)
- Temperature limit and trip in PLC
Readout to MLCR
- Mechanical support for the filter
Extend trench water leak sensorneeds readout #1889- Archiving and alarms: these now go via the Beamline spreadsheet #1880 as the Loading-Bay chiller/de-min loop are for the conventional magnets only
Updated by Nebrensky, Henry about 7 years ago
- File Grundfos_Manual_CRE_CRIE_CRNE_CRTE_SPKE_MTRE_CME_BMS_-_1662523.pdf Grundfos_Manual_CRE_CRIE_CRNE_CRTE_SPKE_MTRE_CME_BMS_-_1662523.pdf added
Pump 1 keeps dropping to low pressure.
Updated by Nebrensky, Henry about 7 years ago
- File 204-72021-2.pdf 204-72021-2.pdf added
- File 204-72021-3.pdf 204-72021-3.pdf added
Drawings
Updated by Nebrensky, Henry about 7 years ago
- File 204-72021-1a.pdf 204-72021-1a.pdf added
The pumps are fitted with 0-16 bar sensors, but they cannot provide much more than 7 bar as the flow is too high.
Pump 1 was showing an alarm light. Paul Masterson connected to the pump via the IR dongle and found the alarm was due to the input signal: "Setpoint Signal Out Of Range", most recently at 22:38 on 19 November 2016, and before that 04:38 on 19 November 2016. We were able to re-set the error (eLog 4219 ). These times correspond to particularly low drops in supplied pressure. We hypothesize that the 4-20 mA setpoint connection is poor and occasionally drops out completely (0 mA, which is indeed out of range).
Disconnecting the 4-20 mA connection from the pump caused it to drop down into a low-flow idle state. We had to locally configure the pumps themselves to ignore external set values, after which it was possible to configure them with a local set value via the IR dongle. We have demonstrated that this value persists even if the pump is power cycled. It will be lost if the arrow buttons on the pump are used
We set a pressure of about 5.9 bar within each pump, giving a circuit pressure of 5.3 bar. We then demonstrated that if the pump was powered off and then powered back on it would start up and run at the appropriate pressure, for both pumps. This means that we are now able to swap easily between the two pumps, just by powering only the desired pump.
Updated by Nebrensky, Henry about 7 years ago
Craig has ordered an R100 remote control unit - this means that MICE should be able to query the pumps for their status and alarm history ourselves, rather than needing to wait for an expert.
Updated by Nebrensky, Henry almost 7 years ago
Yesterday we increased the flows through Q5 and Q8 which caused the circuit pressure to fall to 5.2 bar; then used R100 to increase pump 2 setpoint to 6 bar to get circuit back to 5.4 bar.
Have also found "Setpoint Signal Out Of Range" errors in pump 2 logs.
Updated by Nebrensky, Henry almost 7 years ago
See eLog thread from entry 4389
Essentially, seem to have gradually been losing PLC/C&M functionality, to the extent that we now have one pump completely separated from the control system so that we can control it directly, and no working monitoring of the circuit.
Updated by Nebrensky, Henry over 6 years ago
On 2nd Feb we asked Rob Searle to come down and help Ajit understand the communications between the soft-IOC and the Trench Water
PLC as we were only seeing zeroes in the EPICS panel. The issue turned out to be that some of the data within the
controller had somehow been overwritten with zeroes, though the program itself had remained (through several power
cycles), and the PLC was therefore returning zeroes to the IOC.
Rob Searle reset the PLC and we got the IOC and control panel working. ( eLog 4525 )
Since then the PLC appears to have been working, or at least we've been getting the feedback (pump pressure, etc.) and no problems from the Trench water side during the data run.
Updated by Nebrensky, Henry over 6 years ago
- Status changed from Open to Closed
- % Done changed from 0 to 100
All seemed to be working until we started running - then the mixing valve seemed to flip polarity again - 4971
This was NOT associated with any IOC restart or such.
It looks as though the PLC gradually "degrades" for some reason - probably this should be in a new ticket. The rest of the system is fine.